Catalogo Articoli (Spogli Riviste)

OPAC HELP

Titolo:
Effect of electronic anti-fouling treatment on fouling mitigation with circulating cooling-tower water
Autore:
Kim, WT; Cho, YI; Bai, C;
Indirizzi:
Drexel Univ, Dept Mech Engn & Mech, Philadelphia, PA 19104 USA Drexel Univ Philadelphia PA USA 19104 & Mech, Philadelphia, PA 19104 USA
Titolo Testata:
INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER
fascicolo: 5, volume: 28, anno: 2001,
pagine: 671 - 680
SICI:
0735-1933(200107)28:5<671:EOEATO>2.0.ZU;2-V
Fonte:
ISI
Lingua:
ENG
Tipo documento:
Article
Natura:
Periodico
Settore Disciplinare:
Engineering, Computing & Technology
Citazioni:
12
Recensione:
Indirizzi per estratti:
Indirizzo: Kim, WT Drexel Univ, Dept Mech Engn & Mech, Philadelphia, PA 19104 USA Drexel Univ Philadelphia PA USA 19104 Philadelphia, PA 19104 USA
Citazione:
W.T. Kim et al., "Effect of electronic anti-fouling treatment on fouling mitigation with circulating cooling-tower water", INT COMM HE, 28(5), 2001, pp. 671-680

Abstract

The purpose of the present study was to investigate the effect of electronic antifouling (EAF) technology on fouling mitigation in a heat exchanger in an open, cooling-tower system. Two tests were performed in a rectangular heat-transfer channel at 5 cycles of concentration: one without the EAF treatment and the other with the EAF treatment. The fouling resistance in the case with the EAF treatment was about 70% less than that in the case without the EAF treatment at the end of 270-hr tests. (C) 2001 Elsevier Science Ltd.

ASDD Area Sistemi Dipartimentali e Documentali, Università di Bologna, Catalogo delle riviste ed altri periodici
Documento generato il 02/12/20 alle ore 14:29:56