EVALUATION OF SUCTION-LINE LIQUID-LINE HEAT-EXCHANGE IN THE REFRIGERATION CYCLE
Autore:
DOMANSKI PA; DIDION DA; DOYLE JP;
Indirizzi:
NATL INST STAND & TECHNOL GAITHERSBURG MD 20899 GIANT FOOD INC WASHINGTON DC 20013
Titolo Testata:
International journal of refrigeration
fascicolo: 7, volume: 17, anno: 1994,
pagine: 487 - 493
SICI:
0140-7007(1994)17:7<487:EOSLHI>2.0.ZU;2-E
Fonte:
ISI
Lingua:
ENG
Keywords:
REFRIGERATING CYCLE; HEAT EXCHANGER; GAS; LIQUID; REFRIGERANT; PERFORMANCE;
Tipo documento:
Article
Natura:
Periodico
Settore Disciplinare:
Science Citation Index Expanded
Science Citation Index Expanded
Citazioni:
12
Recensione:
Indirizzi per estratti:
Citazione:
P.A. Domanski et al., "EVALUATION OF SUCTION-LINE LIQUID-LINE HEAT-EXCHANGE IN THE REFRIGERATION CYCLE", International journal of refrigeration, 17(7), 1994, pp. 487-493

Abstract

The paper presents a theoretical evaluation of the performance effects resulting from the installation of a liquid-line/suction-line heat exchanger (LLSL-HX). It examines cycle parameters and refrigerant thermodynamic properties that determine whether the installation results inimprovement of COP and volumetric capacity. The study shows that the benefit of application of the LLSL-HX depends on a combination of operating conditions and fluid properties - heat capacity, latent heat, and coefficient of thermal expansion - with heat capacity being the mostinfluential property. Fluids that perform well in the basic cycle aremarginally affected by the LLSL-HX, and the impact on the coefficientof performance and volumetric capacity may be either positive or negative. Fluids performing poorly in the basic cycle benefit from the LLSL-HX installation through increase of the coefficient of performance and volumetric capacity.

ASDD Area Sistemi Dipartimentali e Documentali, Università di Bologna, Catalogo delle riviste ed altri periodici